Difference between revisions of "CIS OnCall and Troubleshooting"
Jump to navigation
Jump to search
(Created page with " == Beam Noise == : FastSEE BPM Mode # To start : Accel Menubar => EDM => BPM => New FastSEE Control # Choose a BPM by selecting corresponding ioc e.g. iocse11 # Parameters * ...") |
|||
Line 1: | Line 1: | ||
== Beam Noise == | == Beam Noise == | ||
− | : FastSEE BPM Mode | + | : Use FastSEE BPM Mode to diagnose intensity and position from injector BPM's |
# To start : Accel Menubar => EDM => BPM => New FastSEE Control | # To start : Accel Menubar => EDM => BPM => New FastSEE Control | ||
+ | # MAC or Channel Access is required | ||
# Choose a BPM by selecting corresponding ioc e.g. iocse11 | # Choose a BPM by selecting corresponding ioc e.g. iocse11 | ||
− | # | + | # Sampling rate 4 micro-seconds and frequency of sampling is the display rate |
− | + | :: BPMSEE mode | |
− | + | Non-invasive | |
− | + | BPM spikes update correctly | |
− | + | Less samples limit to lower frequency | |
+ | Make sure FastSee Light is ON | ||
+ | :: FastSEE mode | ||
+ | Invasive | ||
+ | BPM spikes update erratically | ||
+ | More samples for higher frequency ~60kHz |
Revision as of 13:42, 18 March 2015
Beam Noise
- Use FastSEE BPM Mode to diagnose intensity and position from injector BPM's
- To start : Accel Menubar => EDM => BPM => New FastSEE Control
- MAC or Channel Access is required
- Choose a BPM by selecting corresponding ioc e.g. iocse11
- Sampling rate 4 micro-seconds and frequency of sampling is the display rate
- BPMSEE mode
Non-invasive BPM spikes update correctly Less samples limit to lower frequency Make sure FastSee Light is ON
- FastSEE mode
Invasive BPM spikes update erratically More samples for higher frequency ~60kHz