Difference between revisions of "CIS OnCall and Troubleshooting"

From Ciswikidb
Jump to navigation Jump to search
(Created page with " == Beam Noise == : FastSEE BPM Mode # To start : Accel Menubar => EDM => BPM => New FastSEE Control # Choose a BPM by selecting corresponding ioc e.g. iocse11 # Parameters * ...")
 
Line 1: Line 1:
  
 
== Beam Noise ==
 
== Beam Noise ==
: FastSEE BPM Mode
+
: Use FastSEE BPM Mode to diagnose intensity and position from injector BPM's
 
# To start : Accel Menubar => EDM => BPM => New FastSEE Control
 
# To start : Accel Menubar => EDM => BPM => New FastSEE Control
 +
# MAC or Channel Access is required
 
# Choose a BPM by selecting corresponding ioc e.g. iocse11
 
# Choose a BPM by selecting corresponding ioc e.g. iocse11
# Parameters
+
# Sampling rate 4 micro-seconds and frequency of sampling is the display rate
* Sampling is 4 micro-seconds
+
:: BPMSEE mode
* Frequency of sampling is determined by Display Update Rate
+
Non-invasive
* BPMSEE mode - non-invasive, sampling rate is slower but BPM spikes update correctly; make sure FastSee Light is ON
+
BPM spikes update correctly
* FastSEE mode - invasive, sampling is faster and BPM spikes may update erratically
+
Less samples limit to lower frequency
 +
Make sure FastSee Light is ON
 +
:: FastSEE mode
 +
Invasive
 +
BPM spikes update erratically
 +
More samples for higher frequency ~60kHz

Revision as of 14:42, 18 March 2015

Beam Noise

Use FastSEE BPM Mode to diagnose intensity and position from injector BPM's
  1. To start : Accel Menubar => EDM => BPM => New FastSEE Control
  2. MAC or Channel Access is required
  3. Choose a BPM by selecting corresponding ioc e.g. iocse11
  4. Sampling rate 4 micro-seconds and frequency of sampling is the display rate
BPMSEE mode
Non-invasive
BPM spikes update correctly
Less samples limit to lower frequency
Make sure FastSee Light is ON
FastSEE mode
Invasive
BPM spikes update erratically
More samples for higher frequency ~60kHz