Difference between revisions of "Meeting 10/12/16"
From Cryowiki
Jump to navigationJump to search (Created page with "Action Items from 10/7 meeting 1. Quantify the oil carryover? (Alicia) Data gathering ongoing for C9 and other machines; ~1 order of magnitude difference between oil removed...") |
|||
Line 2: | Line 2: | ||
1. Quantify the oil carryover? (Alicia) | 1. Quantify the oil carryover? (Alicia) | ||
− | Data gathering ongoing for C9 and other machines; ~1 order of magnitude difference between oil removed at 4th coalescer between CHL C9 and HDR C1. | + | *Data gathering ongoing for C9 and other machines; ~1 order of magnitude difference between oil removed at 4th coalescer between CHL C9 and HDR C1. |
− | + | *Does it improve the oil removal to leave the drain valves slightly open? | |
− | Does it improve the oil removal to leave the drain valves slightly open? | ||
2. What are the options for the oil sensors and would using a different oil sensor work better? (Nate) | 2. What are the options for the oil sensors and would using a different oil sensor work better? (Nate) | ||
− | + | *ULTRASONIC | |
− | + | *CAPACITIVE | |
− | + | *FLOAT SWITCH | |
Visual indication of whether the automated control is working?? | Visual indication of whether the automated control is working?? | ||
3. Flush the oil. (Mat) | 3. Flush the oil. (Mat) | ||
− | On hold until more data can be collected with existing oil. | + | *On hold until more data can be collected with existing oil. |
4. Check the piping for oil after the final oil coalescer with a swab. (Nate) | 4. Check the piping for oil after the final oil coalescer with a swab. (Nate) | ||
− | Will be done during shutdown for oil change. | + | *Will be done during shutdown for oil change. |
5. Check the orifice size on the compressor. (Alicia) | 5. Check the orifice size on the compressor. (Alicia) | ||
− | Alicia contacted manufacturer and importer for this information. | + | *Alicia contacted manufacturer and importer for this information. |
6. Pump Oil out of compressors C7 and C8. (Alicia) | 6. Pump Oil out of compressors C7 and C8. (Alicia) | ||
− | Withdrawing as much mineral oil as possible: will follow up with Isaac's crew to investigate. On hold until immediately before ready to install. Plan is to do an initial run for some duration, then replace oil (approximates a flush). | + | *Withdrawing as much mineral oil as possible: will follow up with Isaac's crew to investigate. On hold until immediately before ready to install. Plan is to do an initial run for some duration, then replace oil (approximates a flush). |
7. Add fitting to the tubing from the oil coalescer drain valves back to the compressor body. (Nate) | 7. Add fitting to the tubing from the oil coalescer drain valves back to the compressor body. (Nate) | ||
− | Options exist. | + | *Options exist. |
Latest revision as of 09:33, 12 October 2016
Action Items from 10/7 meeting
1. Quantify the oil carryover? (Alicia)
- Data gathering ongoing for C9 and other machines; ~1 order of magnitude difference between oil removed at 4th coalescer between CHL C9 and HDR C1.
- Does it improve the oil removal to leave the drain valves slightly open?
2. What are the options for the oil sensors and would using a different oil sensor work better? (Nate)
- ULTRASONIC
- CAPACITIVE
- FLOAT SWITCH
Visual indication of whether the automated control is working??
3. Flush the oil. (Mat)
- On hold until more data can be collected with existing oil.
4. Check the piping for oil after the final oil coalescer with a swab. (Nate)
- Will be done during shutdown for oil change.
5. Check the orifice size on the compressor. (Alicia)
- Alicia contacted manufacturer and importer for this information.
6. Pump Oil out of compressors C7 and C8. (Alicia)
- Withdrawing as much mineral oil as possible: will follow up with Isaac's crew to investigate. On hold until immediately before ready to install. Plan is to do an initial run for some duration, then replace oil (approximates a flush).
7. Add fitting to the tubing from the oil coalescer drain valves back to the compressor body. (Nate)