Difference between revisions of "AIEC Deployment"
Jump to navigation
Jump to search
Line 33: | Line 33: | ||
*Half of the CDC was kept at fixed default HV. | *Half of the CDC was kept at fixed default HV. | ||
*Temp fixed at 299 or 300K until FDC LV brought temp into trained region | *Temp fixed at 299 or 300K until FDC LV brought temp into trained region | ||
+ | |- | ||
+ | |CPP | ||
+ | |June 2022 | ||
+ | |[https://halldweb.jlab.org/wiki/index.php/CPP_DAQ/Monitoring_Test_Spring_2022#AIEC_planning CPP plans] | ||
+ | | | ||
+ | *GPR with MLP (multilayer perceptron) learned prior, trained on GlueX-2020 + PrimEx2021 | ||
+ | *Uncertainty quantification used to determine when to return to the comfort zone (3%: is threshold for standard_deviation_of_prediction/ideal_GCF) | ||
+ | *Default HV 2125V | ||
+ | *HV predictions rounded to nearest 1V | ||
+ | */group/halld/AIEC/utilities/CDC_control_ai/cpp/d_cdc_modelneeds/gpflow_params.pkl | ||
+ | | | ||
+ | *RoboCDC summoned by DAQ 'GO' to read EPICS and set HV. | ||
+ | *RoboCDC scaled the HVB current reading to what it would have been at the default HV, before predicting GCF. | ||
+ | *Overall on/off switch added to CDC HV control gui. | ||
+ | [https://halldweb.jlab.org/wiki/index.php/CPP_DAQ/CPP_AIEC_config CPP AIEC CONFIG] | ||
|- | |- | ||
|} | |} |
Revision as of 00:55, 7 June 2022
Experiment | Date | Wiki & reports | Model | Other details |
PrimEx | Oct-Nov 2021?? | PrimEx_instructions |
|
|
Cosmics | March 2022 | Cosmics_test_plans |
|
|
CPP | June 2022 | CPP plans |
|
|
Experiment | Date | Wiki & reports | Model | Other details |
PrimEx | Oct-Nov 2021?? | PrimEx_instructions |
|
|
Cosmics | March 2022 | Cosmics_test_plans |
|
|
CPP | June 2022 | CPP plans |
|
|